福建大程电机专业制造无刷发电机|柴油发电机组|静音发电机组|汽油发电机|移动电站等

products
   
  1. High Voltage Diesel Generator Set

High Voltage Diesel Generator Set

  • 额定功率1000KW-2250KW

HighVoltageDieselGeneratorSetHighvoltagedieselgeneratorsetcanbeusedasthefrequently-usedpowersupplyandemergencypowersupplyofcommunicationandpowerlightinginthesectorofdatacenters,glass,electronics,paper

  1. 详细信息

High Voltage Diesel Generator Set

High voltage diesel generator set can be used as the frequently-used power supply and emergency power supply of communication and power lighting in the sector of data centers, glass, electronics, papermaking, defense, telecommunications, hospitals hotels, commercial buildings, mining, transportation, etc.

Features

 

Application Range of High Voltage Diesel Generator Set

High voltage diesel generator set can be used as the frequently-used power supply and emergency power supply of communication and power lighting in the sector of data centers, glass, electronics, papermaking, defense, telecommunications, hospitals hotels, commercial buildings, mining, transportation, etc.

 

 

Features of High Voltage Diesel Generator Set

 

The high voltage diesel generator set is available for dual purpose diesel and heavy oil. It is featured with the characteristics of high voltage regulation precision, good dynamic performance, small voltage wave distortion, high efficiency, compact structure, easy maintenance, reliable operation, long service life, good economic performance and so on; in addition, multiple operation of several sets can be realized and the generator room can be built together; line loss in power transmission and distribution is small and there is no problem of transport heating; large initial investment and low maintenance costs make it have obvious advantages for large capacity and long distance power transmission and distribution.

Function of High Voltage Diesel Generator Set

1) brushless self-excitation, H-class insulation, temperature resistance can be up to 180 ℃, providing the guarantee for the operation of generator in harsh environments; 
2) the engine base is steel welded structure, end cover is casting, installation structural style includes two types single bearing and double bearings;
3) the stator adopts 23 pitch winding, which can effectively inhibit the output voltage wave distortion and reduce magnetic field heating; 
4) the rotor is dynamically balanced before assembly, sound damping winding helps to reduce voltage deviation and heat under non-constant load;
5) the output power of the exciter rotor is transported to the host rotor through three-phase full-wave rectifier, the rectifier is protected by a surge suppressor to avoid the damage caused by the short circuit or the phase step out in parallel; 
6) automatic voltage regulator (AVR) protects the engine automatical off-loading, which allows applying full load to engine one-time. Its steady-state voltage regulation can be better than ± 1% so that the generator has high motor starting capability and vulnerability to jamming to non-linear wave distortion; 
7) telephone influence factor TIF is less than 50, telephone harmonic factor THF is less than 2%, brushless device and high quality AVR device can ensure that the interference to radio transmission is very small;
8) the general output has 12 leads, which have a variety of voltage connections. Common type 400200V--50 Hz and 480240V-60Hz; 
9) the generator can be used for 50Hz (1500rmin) operation, also for 60Hz (1800rmin) operation;
10) the generator can be connected to single phase, but the single-phase power is only 60% of the power of three-phase; 
11) the standard protection class is IP21, it can also be made into IP22 or IP23 according to users’ requirements ; when it is IP23, the power will drop by about 5%.

Technical data
Genset Model Power(kW) Rated Current(A) Diesel Model Diesel Power (kW) Cylinder Diameter (mm) Stroke(mm) Displacemint
(L)
Specific Oil Consumption (g/kw.h) 100% Load Specific Fuel Consumption (g/kw.h)
6300V 400V 10500V
DCGY-1000GF 1000 114.6 1804 68.7 G6300ZD 1125 300 380 161 2.16 204
DCGY-1250GF 1250 143.2 2255 85.9 G8300ZD 1500 300 380 215 2.16 204
DCGY-1600GF 1600 213 2886.7 110 G8300ZD13 1765 300 380 215 2.16 204
DCGY-2000GF 2000 229 3608 137.5 G8300ZD16 2206 300 380 215 2.16 204
DCGY-2250GF 2250 239 3960 150 G8300ZD18 2250 300 380 215 2.16 204